Specifications |
||||
Description |
Walk in |
Non Walk in |
||
Standard |
EN / IEC |
61330 / 61330 |
61330 / 61330 |
|
Rated Voltage |
kV |
12 / 24 / 36 |
12 / 24 / 36 |
|
Rated Insulation Voltage |
kV |
12 / 24 / 36 |
12 / 24 / 36 |
|
Rated Short Time Withstand Current |
kA |
16/20/25 |
16/20/25 |
|
1 Min. Power Frequency |
kV |
28 / 50 / 70 |
28 / 50 / 70 |
|
Lightning Impulse Withstand Voltage |
kV |
75 / 125 / 170 |
75 / 125 / 170 |
|
Rated Power of Transformer |
kVA |
Up to 1600 ( Other power on request ) |
||
Compact Substation Dimension / Wide |
mm |
1730 to 3830 |
2450/3050/3150 |
|
Compact Substation Dimension / Height |
mm |
1469 to 2626 (up to 1600kVA) |
1900/2200/2460 (up to 1600kVA) |
|
Compact Substation Dimension / Depth |
mm |
1430 to 2330 |
1850/2200/2350 |
|
Degree Of Protection |
IP |
54 |
54 |
|
Eye Bolt |
P |
P |
||
Colour Shade |
RAL |
7032 / 7035 |
7032 / 7035 |
|
Coating Thickness |
m |
80 - 100 |
80 - 100 |
|
Painting Procedure |
Electro Static – Powder Paint (UV Protected) |